Single Interlock Pre-Action Valve Electric Release System
Construction
The BERMAD Model FP 400E-7M utilizes an elastomeric deluge valve,
designed for advanced fire protection systems and the latest industry standards.
The Single Interlock Electric Release is suitable for use in systems requiring that water be kept out of the sprinkler piping until an electric detecting device is activated.
Single Interlock Pre-Action Systems include automatic sprinklers attached to a dry sprinkler piping system, with a supplementary electric detection system installed in the same area. This system admits water into the sprinkler piping upon activation of the detection system. Water is discharged only through sprinklers that have been opened due to excessive heat.
When a Supervised System is required, a pneumatic low pressure supply shall be provided through a proper Air Maintenance Device (AMD-74 or 75), also an anti-flooding feature is provided by utilizing an in-line check valve, which creates an intermediate vented chamber using a Normally Open drip-check.
Need more information? Contact us here

- Safety and reliability
- Time proven, simple design with a fail safe actuation
- Single piece rugged elastomer, VRSD technology
- Obstacle-free, uninterrupted flow path
- No mechanical moving parts
- Reduced valve opening time, enabling faster fire suppression
- Quick and easy maintenance
- In-line serviceable
- Fast and easy cover removal
Typical Applications
- Water sensitive material storage
- Computer and electronics rooms
- Libraries museums and archives
Additional Features
- PS : Pressure Switch
- ZS : Limit Switch Assembly
- I : Visual Valve Position indicator
- W : Water Motor Alarm
- AMD : Air Maintenance Device